MR483000HG2B-GS Rectifier Module of Telecom Power System
MR483000HG2B-GS is a power supply device that converts standard AC voltage into stable 48Vdc for
communication power supply system.
For a larger load capacity, the rectifier modules can be connected in parallel, or an additional independent monitoring module can be used for intelligent control.
The rectifier module is a plug-in modular unit designed to be compatible with racks and cabinets.
Appearance of Telecom Power System
Module introduction of Telecom Power System
Reliability | |
MTBF | >500,000 hours (25℃) |
Audible Noise | |
Specification | ≤55dB(A) (40℃) |
Interface description of Telecom Power System
Definition of module gold finger of Telecom Power System
Pin number | Pin function description |
1,2 | Output 48V- |
3,4 | Pre-charge |
5,6 | Output 48V+ |
7 | Group address wire of rectifier |
8 | Group inner address wire of rectifier |
13 | CANL |
14 | CANH |
31,32 | module protection ground |
33,34 | AC input neutral( N) |
35,36 | AC input phase line( L) |
Module panel introduction of Telecom Power System
Description of the indicator lights of the rectifier module of Telecom Power System
Indicator | Indicator color | Status | Status description | Suggested solution |
Power indicator |
Green | On | Module AC input is normal | Normal state, no action required |
Off | The AC input of the module is abnormal (no input power supply, input power supply over-voltage and under-voltage, etc.) | Check whether the input is normal; if the input is normal, replace the rectifier module | ||
4Hz flashing (4times/sec) | Manual query status | Normal state, no action required | ||
Alarm indicator |
Yellow | Off | No abnormal alarm | Normal state, no action required |
On | Temperature pre-alarm (ambient temperature exceeds 65℃ ~ over-temperature shutdown) | Check whether the ventilation of module are blocked and whether the ambient temperature is normal | ||
Dormancy shutdown (when the module is in dormancy shutdown, only the protection indicator is on, and the module does not report an alarm) |
Normal state, no action required | |||
290Vac<Input voltage<300Vac | Check if the input voltage is normal | |||
Module current limiting | Normal state, no action required | |||
4Hz flashing (4times/sec) | Module hardware address error | Check if module is inserted in place and locked | ||
0.5Hz flashing (1times/2s) | The communication between the module and the outside is interrupted | Replace the rectifier module or monitoring module; check the CAN bus wiring of the power system for errors | ||
Fault indicator |
Red | Off | No abnormal alarm | Normal state, no action required |
On | The output is locked due to over-voltage or the module is not inserted in place | Unplug the rectifier module, wait for more than 1 minute, and then insert it | ||
No output caused by internal fault of rectifier module | Replace the rectifier module |