Tianjin Estel Electronic Science and Technology Co.,Ltd

TIANJIN ESTEL ELECTRONIC SCIENCE AND TECHNOLOGY CO.,LTD (ESTEL(GUANGDONG) TECHNOLOGY CO., LTD) We are the professoinal supplier of outdoor telecom cabinet, air conditioner, heat exchanger, and telecom

Manufacturer from China
Verified Supplier
10 Years
Home / Products / Telecom Power System /

3KW Photovoltaic Input Communication Solar Module for Telecom Power System

Contact Now
Tianjin Estel Electronic Science and Technology Co.,Ltd
Visit Website
City:shenzhen
Province/State:guangdong
Country/Region:china
Contact Person:MsFiona Liang
Contact Now

3KW Photovoltaic Input Communication Solar Module for Telecom Power System

Ask Latest Price
Video Channel
Brand Name :ESTEL
Model Number :MS483000HG
Certification :ISO9001, CE, 3C, FCC, TLC
Place of Origin :Shenzhen, China (Mainland)
MOQ :1
Price :negotiation
Payment Terms :L/C, D/A, D/P, T/T, Western Union
Supply Ability :20,000 sets per month
Packaging Details :carton/wooden case
Input voltage :120Vdc to 425Vdc (starting voltage greater than 160Vdcÿ
Rated input voltage :340Vdc
MPPT voltage range :120Vdc to 340Vdc
Maximum input :17A
current surge current :EN/IEC61000-4-5
MPPT accuracy :≥99%@load≥400W
Anti-polar protection :Input polarity error, no damage
Insurance :Positive and negative pole insurance
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Electrical specifications

1.1 Input characteristics

input voltage

120Vdc to 425Vdc (starting voltage

greater than 160Vdc)

Rated input voltage 340Vdc
MPPT, voltage range 120Vdc to 340Vdc
Maximum input current 17A
surge current Meet the standard: EN/IEC61000-4-5
MPPT accuracy ≥99%@load≥400W
Anti-polar protection Input polarity error, no damage
Enter the insurance

Positive and negative pole insur-

ance

maximum input voltage 450Vdc (power supply cannot be damaged)

1.2 output characteristic

1.2.1 Output voltage current adjustment rate

output voltage +54.5Vdc

Output voltage setting

value

+54.5±0. 1Vdc
Output voltage adjusta- ble range +42Vdc+58Vdc
productiveness ≥96%@340Vdc/40%~70% Load-54.5VDC
Source effect ±0. 1%
Load effect ±0.5%
Stability accuracy ±0.6%
minimum current 0A
rated current 55A@-48VDC
Output limit current setting point 0-62.5A
peak point current 62.5A

Temperature coefficient

(1/ )

≤±0.02%
Battery life 10ms

Standby power consumpt-

ion

4W
Maximum capacitive load 40000uF
Maximum number of para- llel machines 31

Note: The deviation of the setting value of various adjustable voltage and the setting value of protection voltage should not be higher than ±0.1V.

1.2.2 Output ripple and noise

performance index crest value remarks

Ripple and noise

(peak-to-peak)

200mVp-p Bandwidth is less than or equal to 20M

Note: 1) Ripple and noise test: Ripple and noise bandwidth is set at 20 megahertz.

1.2.3 Output dynamic response

Voltage

overshoot

Jumping slope variation in load recovery time

Output overshoot

+54.5V

0. 1A/uS

25% to 50% load, 50%

to 25% load,

50% to 75% load, 75%

to 50% load

≤200us

±5%

+58V 0.1A/uS

0% to 100% load, 100% to 0% load

No overvoltage is triggered

protect

Note: The load jump cycle is 4ms.

1.2.4 The output of the machine is out of control

output voltage variation in load Output overshoot
+54.5V Start overshoot <1%

1.2.5 available machine time

project 340Vdc@25
Power on delay 3S~8S

Note: The time from power on to output voltage to 42Vdc.

1.2.6 Power conversion point

input voltage maximumoutput
200Vdc425Vdc 3000W
120Vdc200Vdc Linear reduction
120Vdc 1800W

Note: When the pv input voltage is 340Vdc~425Vdc, the output power in this range is determined by the PV characteristics.

3KW Photovoltaic Input Communication Solar Module for Telecom Power System

DC input derating curve

1.2.7 Output characteristics

3KW Photovoltaic Input Communication Solar Module for Telecom Power System

Maximum output characteristic curve

1.2.8 Temperature reduction

ambient temperature maximumoutput
-40~50 3000W
5065 Linear reduction
65 2400W
6575 Linear reduction
75 1200W

3KW Photovoltaic Input Communication Solar Module for Telecom Power System

Ambient temperature derating curve

1.2.9 Noise voltage

Noise voltage crest value remarks
Telephone weighing noise voltage 2mV

Broadband noise volt-

age

50mV 3.4150KHz
20mV 15030000KHz

1.3 Defencive function

1.3.1 Output short circuit protection

output voltage remarks

+54.5V

It can be short circuit for a long time, and can be automatically restored after the short circuit disappears

1.3.2 Overvoltage protection output

Overvoltage protection can be categorized into internal overvoltage and external overvoltage protection. Internal overvoltage faults range from 58.5VDC to 60.5 VDC, which can be monitored and set; when a fault occurs, the module will lock out. If the external voltage exceeds 63VDC and remains above this level for more than 500ms, the module will also lock out. Once the system enters the locked-out protection state, the PV power supply must be disconnected before the system can be re-powered to resume operation.

1.3.3 Output under-voltage warning

The range is 37VDC~39VDC. When it i s lower than the under-voltage alarm value, normal output is reported and an alarm is given.

1.3.4 Overvoltage protection input

input voltage remarks

430±5Vdc

Output is turned off and can be

self-recovered after the voltage is

normal

Input recovery point deviation> 15V

1.3.5 Input under-voltage protection

input voltage remarks

110±5Vdc

Output is turned off and can be

self-recovered after the voltage is

normal

Input recovery point deviation> 40V

1.3.6 Underpower protection

Underpower protection logic:

In normal operation, when the input power is less than 50W and lasts for 5 minutes, the under-power flag is set and the machine shuts down. Otherwise (that is, in the shutdown state), when the input voltage is greater than 160V and the bus voltage is greater than 150V for 5 minutes, the under-power flag is cleared and the module restarts.

Minimum module power: 50W

1.3.7 Overtemperature protection

temperature remarks
≤50 The module can output the maximum output power without overtemperature protection, and the module runs normally
50℃~65 Module power is reduced to 2400W linearly
65℃~75 Module power is reduced to 1200W
>75 Shut down, and the self-recovery temperat- ure difference after shutdown is> 10

1.4 Communication function between rectifier module and monito- ring module

The CAN bus communication mode is adopted between the rectifier module and the monitoring module, which supports remote software version upgrade, and the address board can be used to set the address of the module. When the AC input is disconnected, the module needs to communicate with the host.

The CAN interface in the rectifier module needs to adopt an isolation design. The power supply of CAN is +5Vdc, which is provided by the internal rectifier module.

The main monitoring information of the rectifier module is:

1) Voltage regulation and current regulation function: meet the requirements of battery equal float charge, meet the voltage regula- tion requirements;

2) Single module on/off control;

3) Protection and alarm information feedback:

Municipal power failure: municipal power failure (over or under voltage of AC input);

Module protection: temperature warning;

Module fault: shutdown due to output overvoltage, fan failure, shutdown due to overheating or no output caused by other internal reasons of the module; (the module is in the sleep shutdown state, and the module fault is not reported due to mains failure).

1.5 LED indicator

The power LED indicator is installed on the side of the power panel, and the output status is shown in the following table.

Indicative

signs

Color of

the indicator light

normal

state

unusual

state

Anomaly

reason

Power operation refers to Indicator

light

hispid

arthraxon

bright

go out

Photovoltaic input

fault (no DC input, DC input over or under voltage), module no output.

Protect the

indicator

light

yellow

go out

bright

Temperature warning

(environmental tempe- rature exceeds 65 ~ shutdown over temper- ature);

Sleep shutdown (when the module is in sleep shutdown, only the

protection indicator

light is on and the module does not report alarm). Communication interruption (the pr- otection indicator

light flashes)

fault indicating lamp

red

go out

bright

Output overvoltage

shutdown, fan failure, overheating shutdown, no output caused by internal reasons of the module.

3KW Photovoltaic Input Communication Solar Module for Telecom Power System

Inquiry Cart 0