Tianjin Estel Electronic Science and Technology Co.,Ltd
TIANJIN ESTEL ELECTRONIC SCIENCE AND TECHNOLOGY CO.,LTD (ESTEL(GUANGDONG) TECHNOLOGY CO., LTD) We are the professoinal supplier of outdoor telecom cabinet, air conditioner, heat exchanger, and telecom
Add to Cart
9U Large Capacity Embedded Power Supply Standard 19-inch Rack or Built-in Cabinet
1. 9U Large Capacity Embedded Power Supply Features
DC Rectifier System supply 9U height compact design to meet critic
alapplication needs of fiber and microwave transmission, access device,
switch. The system maximum power is 300A, with customized AC/battery/load MCBs.
The cables are front accessing with MCB and busbar
2. 9U Telecom Power Supply Parameter
Model | ETP48300 | |
System | Dimension(mm) | 482.6(W)x350.6(D)x9U(H) |
Weight | ≤ 50kg(without rectifier module) | |
Cooling mode | Forced air cooling | |
Installation mode | Installed on 19-inch rack or inside the cabinet | |
IP Grade | IP20 | |
AC Distribution | Input voltage | 380VAC, three phase |
Input capacity | 2x63A/4P | |
Input frequency | 45~65Hz, rated 50/60Hz | |
AC SPD | 20kA/30kA, 8/20μs | |
DC Distribution | Output voltage | -42~-58VDC, rated value: -53.5VDC |
Maximum capacity | 18kW(6x3000W rectifier module) | |
Battery breakers | 2x125A/1P | |
Load breakers | User 1: LLVD1: 1×125A/1P, 1×63A/1P, 1×16A/1P, 1×6A/1P; BLVD1: 1×63A/1P; User 2: LLVD2: 1×63A/1P, 2×16A/1P, 1×6A/1P; BLVD2: 1×63A/1P; User 3: LLVD3: 1×63A/1P, 2×16A/1P, 1×6A/1P; BLVD3: 1×63A/1P; User 4: LLVD4: 1×63A/1P; BLVD4: 3×10A/1P; | |
DC SPD | 10kA/20kA, 8/20μs(designed inside) | |
Rectifier Module | Input voltage | 85VAC-300VAC, rated value: 220VAC |
Efficiency | ≥96% | |
Rated power | 3000W(176~300VAC ) | |
Dimension | 106.5mm(W)×286mm(D)×41.5mm(1U/H) | |
Cooling mode | Forced cooling with fan | |
Controller | Signal input | 3 AI(2 battery temp., 1 ambient temp) ,7 DI(SPD, 6 common DI) |
Alarm output | 6 dry contact | |
Communication port | RS485/LAN Ethernet/SNMP | |
Display mode | LCD | |
Environment | Operating temperature | -40℃~+65℃ |
Storage temperature | -40℃~+70℃ | |
Operating humidity | 5%~95%(non-condensing) | |
Altitude | 0~3000m(If the altitude is within the range of 2000m to 3000m, the maximum operating temperature decreases by 1℃ as the altitude increases by 200m.) |
3. ESTEL 48v Telecom Power Supply
A rectifier converts alternating current (AC) to direct current (DC) and provides the power necessary to charge batteries. With a focus on continuously improving the total cost of ownership, ESTEL’s rectifiers, combined with advanced control and monitoring features, help reduce both capital and operational expenditure. Our rectifiers boast excellent power density while fulfilling space and weight requirements. They leave plenty of room for other equipment and create savings in packaging and transportation costs. In addition, their high efficiency lowers total energy consumption and reduces carbon footprint.
ESTEL’s rectifiers are easy to install, as their connectors are located at the rear and are hot-pluggable. Fan cooling with speed control renders operating almost silent. In general the rectifiers include a wide AC input voltage range, protection against AC overvoltage and optional protection against loss of neutral, which make this solution very reliable even in the regions with AC utility network problems.
4. Product Pictures
Rack mounted pictures for reference:
5. Controller-MC2600 (Monitoring Module)
The MC2600 front panel
(1) LAN port (2) RS485 port (3) Run indicator (4) Minor alarm indicator
(5) Major alarm indicator (6) Handle (7) Buttons
Table for controller button description
Button | Description | |
ESC | Returns to the previous menu without saving the settings. | Press the ESC and ENT button at the same time within a short period of time can restart the controller. |
ENT.
| Ø Enters the main menu from the standby screen. Ø Enters a submenu from the main menu. Ø Saves the menu settings. | |
UP | Turns to the previous menu or sets parameter values. When setting parameter values, you can hold down this button to quickly adjust values. | When the parameter value is set by multiple string types, press up or down button to change each value. After setting the value, press the confirm button to move the cursor back automatically. |
DN. | Turns to the next menu or sets parameter values.When setting parameter values, you can hold down this button to quickly adjust values. |
Describes the indicator on the controller panel is shown in table below
Type | Color | State | Instructions |
Run indicator | Green | Flickering | Controller is running properly |
Off | Controller is fault or has no DC input | ||
Minor Alarm | Yellow | Normally on | The controller generates a minor alarm |
Off | The controller does not generate any minor alarms | ||
Major alarm | Red | Normally on | The controller generates a major alarm |
Off | The controller does not generate any major alarms |
The controller provides two communication ports
The definition of RS485 communication port is shown in below table
Pin No. | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Signal name | RS485+ | - | RS485- | - | - | - | - | - |
The LAN Ethernet port interface definition is shown in Table
Pin No. | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Signal name | TX+ | TX- | RX+ | - | - | RX- | - | - |
6. Subrack Installation
Install the subrack to the 19-inch rack, as shown in Figure below.
Ø Step 1,Remove the plug from the package.
Ø Step 2,Push the plug into the 19-inch rack
Ø Step 3,Install the fixed screw (if the mounting hole of the plug frame ear does not correspond to the position of the floating nut of the frame,
it needs to be adjusted according to the actual installation).
Install Rectifier/Solar module
Ø Step 1, Take out the module from the package.
Ø Step 2, Hold the module handle on the front panel and put the module onto the slot.
Ø Step 3, Push the module slowly to the front panel of the module and flush with the power
distribution panel.
Ø Step 4, Tighten the fixing screw on the module panel so that the module does not come off.