5000W Cooling Capacity R134A Refrigerant Kiosk Air Conditioner With 1000W Heating Capacity
1.Technical Parameters
Designed for outdoor advertising machine cooling, easy to install, good air conditioning duct system design, effectively solve the high temperature black screen phenomenon;
Low noise, anti fouling, IP55 protection, etc;
Working environment range: - 40~+ 55 ℃;
Multi function alarm output and RS485 communication function;
Adopt famous brand industrial parts with high reliability;
Fast man-machine interface operation, real-time temperature display,automatic precision Ensure temperature control.
2. Product Key Parameters
Item | Name | Unit | Parameter |
Dimension and installation | Body outline dimension (width*height*depth ) | mm | 1004*729*325 |
Outline dimension including flange(width*height*depth ) | mm | / | |
Weight | Kg | 58 | |
Installation method | Door Mounted | ||
Installation method | Outdoor | ||
Environment and protection | Working environment temperature | ℃ | -40 to +55 |
Noise | dB(A) | 65 | |
Life expectancy | Years | >10 | |
IP grade | IP55 | ||
Refrigerant | R134a | ||
ROHS certification | yes | ||
Performance | Input voltage range | 220 VAC±15% ~/50Hz | |
Refrigerating capacity(L35/L35) | W | 5000 | |
Rated Refrigerating input power(L35/L35) | W | 1700 | |
Rated Refrigerating current (L35/L35) | A | 7.7 | |
Maximum Refrigerating current | A | 10.5 | |
Heat capacity(optional) | W | 1000 | |
Air Volume of Inner Circulation | m3/h | 1500 |
3. Product Dimensions
4. Preparation And Installation
4.1 Removing package and checking
Please prepare installation tools: knife and scissors, and wear protective gloves.
Please remove wrapping film and packing belt, then remove the carton, take out the air conditioner.
Please check the attachment list and accessory bags in the carton, check whether the air conditioner model is right .
4.2 Mechanical Installation
Installation tool: Phillips screwdriver
Installation Steps:
Choose cut location on the cabinet according to the holing diagram, remove the shadow area and make the installation hole.
Make air conditioner flange close to cabinet door, Fix the air conditioner on the installation surface of the cabinet firmly with M5 screws.
Check whether air conditioner is installed levelly and firmly.