Brand Name :ESTEL
Model Number :HE06-30SEH/T
Certification :ISO9001, CE, 3C, FCC, TLC
Place of Origin :Shenzhen, China (Mainland)
MOQ :1
Price :negotiation
Payment Terms :T/T, L/C, etc
Supply Ability :12,000 sets per month
Delivery Time :10-15 working days
Packaging Details :carton + foam + wooden case +pallet
Cooling Method :heat pipe, passive cooling
Installation Mode :top mounted
Protection Level :IP55
Cover Material :galvanized steel
Rated Input Power :46W
Rated Input Current :0.95A
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

300W Outdoor Network Cabinet Heat Exchanger Low Noise ISO9001 CE Certification

Quick Details:

Place of Origin: Shenzhen, China (Mainland) Rated Heat Exchange Capacity: 30W/K
Brand Name: ESTEL Rated Heating Capacity:300W
Model: HE06-30SEH/T Input Voltage: DC48V
Product Name: Outdoor Telecom Cabinet Heat Exchanger Rated Input Current: 0.95A
Certification: ISO9001, CE, 3C, FCC, TLC Rated Input Power: 46W
Protection Level: IP55 Noise: 50dB
Installation Mode: top mounted Dimension W×D×H: 482.6×500×180 mm
Support OEM Type: air to air heat exchanger

Payment & Shipping Terms:

Minimum Order Quantity: 1 set
Price: negotiation
Payment Terms: T/T, L/C, etc
Supply Ability: 12,000 sets per month
Delivery Time: 10-15 working days
Packaging Details: carton + foam + wooden case +pallet

1. Technical Parameters

Model HE06-30SEH/T
Performance Parameters
Rated Voltage (V) DC48V
Rated Current (A) 0.95
Heat Exchange Capacity (W) 300
Heater Power (W) 300
Rated Power (W) 46
Circulation Air Volume (m3/h) 200
Noise (dB(A)) 50
Refrigerant Mixed Liquid
Working Temperature -20°C ~ 55°C
Mechanical Parameters
Installation Mode Top Installed
Height (mm) 180
Width (mm) 482.6
Depth (mm) 500
Controller Parameters
Working Voltage (V) DC36~72
Working Temperature and Humidity -20°C ~ +80°C, <90%RH
Temperature Control Accuracy (°C) 0.1
Power Consumption (W) 5
Communication Mode Dry contact,RS485, RS232, GPRS

2. Description

The cabinet heat exchanger is designed for outdoor cabinet and control cabinet. It is applicable for the scenarios where internal equipment of the cabinet emits a large quantity of heat and the normal operating temperature of internal equipment is higher than the environment temperature and where the indoor environment needs to be isolated from the outdoor completely.

The heat exchanger for outdoor cabinet adapts to the harsh environment. The complete isolation between the indoor environment and the outdoor environment can prevent the dust, hazardous gases, and humid gases from entering the cabinet, thus ensuring the internal cleanliness of the cabinet.

3. Application

The cabinet heat exchanger is widely used for outdoor telecom cabinet, outdoor battery cabinet, outdoor UPS cabinet, outdoor power cabinet, electric cabinet and industry cabinet,etc.

4. Features

(1) Independent energy saving control technology greatly reduces working energy consumption;

(2) LCD control board provides easy installation and maintenance;

(3) Perfect monitoring function, effective monitoring and management on air conditioner operation;

(4) Integrated design, easy for installation and maintenance;

(5) Protection Level: IP55, anti- corrosion, long service life;

(6) Using DC high efficient fans, greatly lower the product noise, environment friendly;

(7) Good energy saving performance, short investment payback period;

(8) Long service life: more than 10 years, easy maintenance and low cost;

(9) With RS485 remote monitoring interface, fault detection and alarm can be transmitted to monitoring center through controller.

5. Electrical Wiring Diagram

300W Outdoor Network Cabinet Heat Exchanger Low Noise ISO9001 CE Certification

Wiring Ports:

0V -48V: power supply input (voltage input: DC36 - 65V)

A+ B- SGND: RS485 communication interface

AL1 AL2: general alarm output

F+ F- : auxiliary direct ventilation control output (output voltage: DC48V)

6. System Control Wiring Diagram

300W Outdoor Network Cabinet Heat Exchanger Low Noise ISO9001 CE Certification

7. Packing and Shipping

300W Outdoor Network Cabinet Heat Exchanger Low Noise ISO9001 CE Certification

Our Delivery Agent

The goods can be shipped by sea, by air, by courier, by land, by train, etc.

Besides the following delivery agent, we can also look for the delivery agent with the best price in china if you need us to do for you.

8. Our Contact Information

Mobile Phone: 0086-13752765943

Telephone: 0086-0755 66600941

Email: info@estel.com.cn

lxf.estel@hotmail.com
Skype: fiona.liang10

Inquiry Cart 0